IEC-60079-31 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t

IEC-60079-31 - EDITION 3.0 - CURRENT
Show Complete Document History

Document Center Inc. is an authorized dealer of IEC standards.
The following bibliographic material is provided to assist you with your purchasing decision:

Included in this current edition are the following subparts:

 EDITION 3.0 - Jan. 11, 2022
 ED. 3.0 CORRIGENDUM 1 - Nov. 1, 2023

IEC 60079-31:2022 is available as IEC 60079-31:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.

IEC 60079-31:2022 is applicable to equipment protected by enclosure and surface temperature limitation for use in explosive dust atmospheres. It specifies requirements for design, construction and testing of Ex Equipment and Ex Components. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document does not apply to dusts of explosives, which do not require atmospheric oxygen for combustion, or to pyrophoric substances. This document does not apply to Ex Equipment or Ex Components intended for use in underground parts of mines as well as those parts of surface installations of such mines endangered by firedamp and/or combustible dust. This document does not take account of any risk due to an emission of flammable or toxic gas from the dust. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. Main significant changes from the previous edition are:
1) Document has been restructured from edition 2
2) Fault current rating of interrupting contacts in clauses 4.3.1 and 4.4.1, major change type C1
3) Cells and batteries in clauses 4.3.5.1 and 4.4.5.1, major change type C2
4) Overload or malfunction condition for the determination of temperature class for "tb" converter fed rotating electric machines, major change type C3
5) Additional requirements for entry devices with dust ignition protection by enclosure "t", major change type C4
Information about the background of .Major Technical Changes.
C1 . Ex Equipment having Level of Protection "ta" shall be rated for connection to a circuit with a prospective short circuit current of not greater than 1.5 kA. For Ex Equipment having Level of Protection "tb" or "tc" which is intended for mains connection and intended to interrupt fault current above 10kA, the equipment shall have a rated maximum short circuit withstand current, be tested according to 6.1.1.1, and be marked according to Clause 7.
C2 . For Ex Equipment having Level of Protection "ta" which contains a cell or battery, only a sealed cell or battery shall be used. For Ex Equipment having Level of Protection "tb" and "tc" where there are sparking contacts or hot surfaces, and which contains a cell or battery, only a sealed cell or battery shall be used.
C3 . Table 2 now includes malfunction conditions for temperature class determination of Level of Protection "tb" converter-fed electric machines.
C4 . Annex A added for entry devices with Type of Protection "t" including cable transit devices.
ORDER

Price:

$143.56        


Want this as a site license?

To find similar documents by classification:

29.260.20 (Electrical apparatus for explosive atmospheres)

This document comes with our free Notification Service, good for the life of the document.

This document is available in either Paper or PDF format.

 

Customers who bought this document also bought:

AS-34591
Connector, Plug, Electrical, Self-Locking, Coupling Nut, Rear Release, Crimp Contact, AN Type

AS-50151
Connectors, Electrical, Circular Threaded, AN Type, General Specification For

AS-39029
Contacts, Electrical Connector, General Specification For

Document Number

IEC 60079-31 Ed. 3.0 b:2022

Revision Level

EDITION 3.0

Status

Current

Publication Date

Jan. 11, 2022

Committee Number

31