ASTM-E741 › Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution
The following bibliographic material is provided to assist you with your purchasing decision:
Scope
1.1 This test method describes techniques using tracer gas dilution for determining a single zone's air change with the outdoors, as induced by weather conditions and by mechanical ventilation. These techniques are: (1) concentration decay, (2) constant injection, and (3) constant concentration.
1.2 This test method is restricted to any single tracer gas. The associated data analysis assumes that one can characterize the tracer gas concentration within the zone with a single value. The zone shall be a building, vehicle, test cell, or any conforming enclosure.
1.3 Use of this test method requires a knowledge of the principles of gas analysis and instrumentation. Correct use of the formulas presented here requires consistent use of units, especially those of time.
1.4 Determination of the contribution to air change by individual components of the zone enclosure is beyond the scope of this test method.
1.5 The results from this test method pertain only to those conditions of weather and zonal operation that prevailed during the measurement. The use of the results from this test to predict air change under other conditions is beyond the scope of this test method.
1.6 The text of this test method references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered requirements of this test method.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Keywords
air change; air change flow; air change rate; air changes per hour; air exchange; air leakage; air leakage rate; concentration; tracer gas; concentration decay; constant concentration; contant injection; envelope; building; exfiltration; infiltration; tracer gas; ventilation; ventilation rate; zone; ICS Number Code 13.040.01 (Air quality in general)
To find similar documents by ASTM Volume:
04.11 (Building Constructions (I): E72 - E2110)
To find similar documents by classification:
13.040.01 (Air quality in general)
This document comes with our free Notification Service, good for the life of the document.
This document is available in either Paper or PDF format.
Customers who bought this document also bought:
IPC-R-700Modification, Rework & Repair of Printed Boards & Assemblies
IPC-A-610
Acceptability of Electronic Assemblies (Hardcopy format)
EIA-568
Commercial Building Telecommunications Cabling Standard
Document Number
ASTM-E0741-24
Revision Level
2024 EDITION
Status
Current
Modification Type
Revision
Publication Date
Aug. 8, 2024
Document Type
Test Method
Page Count
18 pages
Committee Number
E06.41