ASTM-E2931 Standard Test Method for Limiting Oxygen (Oxidant) Concentration of Combustible Dust Clouds

ASTM-E2931 - 2013 R19 EDITION - CURRENT
Show Complete Document History

Document Center Inc. is an authorized dealer of ASTM standards.
The following bibliographic material is provided to assist you with your purchasing decision:

Standard Test Method for Limiting Oxygen (Oxidant) Concentration of Combustible Dust Clouds
ORDER

Price:

$69.00        


Want this as a site license?

Scope

1.1 This test method is designed to determine the limiting oxygen concentration of a combustible dust dispersed in a mixture of air with an inert/nonflammable gas in a near-spherical closed vessel of 20 L or greater volume.

1.2 Data obtained from this method provide a relative measure of the deflagration characteristics of dust clouds.

1.3 This test method should be used to measure and describe the properties of materials in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment that takes into account all of the factors that are pertinent to an assessment of the fire hazard of a particular end use.

1.4 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.

1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. Specific precautionary statements are given in Section 8.

1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

Significance and Use

5.1 This test method provides a procedure for performing laboratory tests to evaluate relative deflagration parameters of dusts.

5.2 Knowledge of the limiting oxygen (oxidant) concentration is needed for safe operation of some chemical processes. This information may be needed in order to start up, shut down or operate a process while avoiding the creation of flammable dust-gas atmospheres therein, or to pneumatically transport materials safely. NFPA 69 provides guidance for the practical use of LOC data, including the appropriate safety margin to use.

5.3 Since the LOC as measured by this method may vary with the energy of the ignitor and the propagation criteria, the LOC should be considered a relative rather than absolute measurement.

5.4 If too weak an ignition source is used, the measured LOC would be higher than the “true” value and would not be sufficiently conservative. This is an ignitability limit rather than a flammability limit, and the test could be described as “underdriven.” Ideally, the ignition energy is increased until the measured LOC is independent of ignition energy (that is, the “true” value). However, at some point the ignition energy may become too strong for the size of the test chamber, and the system becomes “overdriven.” When the ignitor flame becomes too large relative to the chamber volume, a test could appear to result in an explosion, while it is actually just dust burning in the ignitor flame with no real propagation beyond the ignitor (1-3).5 This LOC value would be overly conservative.

5.5 The recommended ignition source for measuring the LOC of dusts in 20-L chambers is a 2500-J pyrotechnic ignitor.6 This ignitor contains 0.6 g of a powder mixture of 40 % zirconium, 30 % barium nitrate, and 30 % barium peroxide. Measuring the LOC at several ignition energies will provide information on the possible overdriving of the system to evaluate the effect of possible overdriving in a 20-L chamber, comparison tests may also be made in a larger chamber such as a 1-m3 chamber (1-3).

5.6 The values obtained by this testing technique are specific to the sample tested (particularly the particle size distribution) and the method used and are not to be considered intrinsic material constants.

Note 1: Much of the previously published LOC data (4). were obtained using a spark ignition source in a 1.2-L Hartmann chamber and may not be sufficiently conservative. The European method of LOC determination EN 14034–4 uses two 1000-J pyrotechnic igniters in the 20-L chamber.

Keywords

dust explosions; inerting; limiting oxygen concentration;; ICS Number Code 13.230 (Explosion protection)

To find similar documents by ASTM Volume:

14.02 (General Test Methods; Forensic Psychophysiology; Forensic Sciences; Terminology; Conformity Assessment; Statistical Methods; Nanotechnology; Forensic Engineering; Manufacture of Pharmaceutical Products)

To find similar documents by classification:

13.230 (Explosion protection Electrical apparatus for explosive atmospheres, see 29.260.20 Explosives and pyrotechnics, see 71.100.30)

This document comes with our free Notification Service, good for the life of the document.

This document is available in either Paper or PDF format.

 

Customers who bought this document also bought:

NAS-410
NAS Certification and Qualification of Nondestructive Test Personnel

ASTM-E1742
Standard Practice for Radiographic Examination

ASTM-E1165
Standard Test Method for Measurement of Focal Spots of Industrial X-Ray Tubes by Pinhole Imaging

Document Number

ASTM-E2931-13(2019)

Revision Level

2013 R19 EDITION

Status

Current

Modification Type

Reapproval

Publication Date

March 8, 2019

Document Type

Test Method

Page Count

9 pages

Committee Number

E27.05