ASTM-D2656 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 2001 to 35 000 V

ASTM-D2656 - 2020 EDITION - CURRENT
Show Complete Document History

Document Center Inc. is an authorized dealer of ASTM standards.
The following bibliographic material is provided to assist you with your purchasing decision:


This specification covers a crosslinked polyethylene insulation for electrical wires and cables for conductor sizes 8 AWG (8.37 mm2) and larger. The base polymer of this insulation consists substantially of polyethylene. The partial discharge, ac voltage, insulation resistance, and dc voltage shall be tested to meet the requirements prescribed. The accelerated water absorption, permittivity and dissipation factor, U-bend discharge, and surface resistivity shall be tested to meet the requirements prescribed. The heat distortion, and percent hot creep and percent hot set shall be tested to meet the requirements prescribed.

ORDER

Price:

$61.00        


Want this as a site license?

Scope

1.1 This specification covers a crosslinked polyethylene insulation for electrical wires and cables for conductor sizes 8 AWG (8.37 mm2) and larger. The base polymer of this insulation consists substantially of polyethylene.

1.2 This type of insulation is suitable for use on power cables in wet and dry locations at conductor temperatures not exceeding 90 °C for continuous operation, 130 °C for emergency overload conditions, and 250 °C for short-circuit conditions. It is considered suitable for all sizes and voltage classifications of single- and multiple-conductor power cables at voltage ratings of 2001 to 35 000 V phase-to-phase at the 100 % insulation level and at voltage ratings of 2001 to 25 000 V at the 133 % insulation level as listed in Table 1C of Test Methods D470.

1.3 Materials covered by this specification are not sunlight- and weather-resistant unless they are carbon black pigmented or contain an additive system designed for this protection.

1.4 In many instances the insulation cannot be tested unless it has been formed around a conductor. Therefore, tests are done on insulated wire in this standard solely to determine the relevant property of the insulation and not to test the conductor or completed cable.

1.5 Whenever two sets of values are stated, in different units, the values in the first set are regarded as standard, while the values in parentheses are provided for information only and are not considered standard.

1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

Keywords

ac voltage; crosslinked polyethylene; dc voltage; heat distortion; hot creep; hot set; insulation resistance; water absorption; weather resistant;

To find similar documents by ASTM Volume:

10.02 (Electrical Insulation (II): D2518 - latest)

To find similar documents by classification:

29.035.20 (Plastics and rubber insulating materials Including adhesive tapes)

This document comes with our free Notification Service, good for the life of the document.

This document is available in either Paper or PDF format.

Document Number

ASTM-D2656-20

Revision Level

2020 EDITION

Status

Current

Modification Type

Revision

Publication Date

Oct. 26, 2020

Document Type

Specification

Page Count

3 pages

Committee Number

D09.07